Input | |
---|---|
Input voltage | 3 ? 360...440 V AC |
Primary fusing external | max. 10 A |
Frequency | 50...60 Hz |
Input current | 3 ? 0.42 A |
General data | |
Standards | EN 60950-1, EN 61204-3, EN 55022 B |
Mounting method | DIN-rail mountable TH35 (EN 60715), additional plate for screw mounting Art.-No. 89500 |
Efficiency | 90% |
Relative humidity | 30...90%, no condensation |
Dimensions H ? W ? D | 132?198?97 mm |
Temperature range | 0...+60 °C (storage temperature -25...+85 °C) |
Output | |
Output voltage | 24 V DC (SELV), ±1%{} 22...28 V adjustable |
Output current | 10 A (+60 °C){} 12 A (+40 °C) |
Mains failure bridging time | min. 3 ms (400 V AC) |
Ripple | max. 20 mVrms |
Spikes | max. 100 mV p-p |
Unit protection | Short-circuit and overload protected |
Phase monitoring | Switching off during 2-phase operation |
LED display | LED (green): in operation{} LED (red): off{} LED (yellow): pre-warning when overheated or overloaded |
Parallel usage/serial usage | yes/yes |
Commercial data | |
country of origin | CZ |
customs tariff number | 85044090 |
EAN | 4048879080637 |
eClass | 27049002 |
Packaging unit | 1 |